MC19-1.20
5.13 Program Example 1
The following sequence of entries creates and runs the program shown graphically below.
1. Turn the controller SP down to ‘0’ by pressing down .
2. Press page until Prog, Segments Used is displayed. On P10 or P25 models press
up or down to select a new program number, (a program with only 1 segment).
3. Press scroll until Holdback Value is displayed. Default ‘0’ degrees.
4. Press scroll until Ramp Units is displayed. Press up or down to set to ‘Min’
5. Press scroll until Cycles is displayed. Default ‘1’
6. Press scroll until Segment 1 is displayed
7. Press scroll until Segment Type is displayed. Press up or down to select
‘Rate’
8. Press scroll until Holdback Type is displayed. Default ‘Off’
9. Press scroll until Target SP is displayed. Press up or down to set to ‘400’
degrees.
10. Press scroll until Ramp Rate is displayed. Press up or down to set to ‘5.0’
degrees per minute.
Repeat steps 6 to 10 for 4 more segments. Set Holdback to the default ‘Off’. Enter the
following parameters and values:
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Step Target SP ‘600’ degrees
Segment Type Dwell Duration ‘30:00.0’ minutes
Segment Type Time Target SP ‘200’ degrees, Duration ‘2:00:0’ hours
Finish the program with an End segment:
11. Press scroll until Segment Type is displayed. Press up or down to select
‘End’
12. Press scroll until End Type is displayed. Press up or down to select ‘Reset’
13. Press page and scroll together to return to the home display.
To run the program either press RUN/HOLD or:
14. Press page until Program Status is displayed
15. Press scroll until the cursor moves to the program status of ‘Reset’
16. Press to select ‘Run’.
Segment 1
Type ‘Rate’
Target 400°
Rate 5.0°/Min
Segment 2
Type ‘Dwell’
Duration
30min
Segment 3
Type ‘Step’
Target 600°
Segment 4
Type ‘Dwell’
Duration
30min
Segment 5
Type ‘Time’
Target 200°
Time 2 hours
Segment 6
Type ‘End’
End type
‘Reset’
400°C
600°C
200°C
5°C/m
30min
30min
2 hours
Time display examples
10:05.3 Min / Sec / 10
th
Sec
24:10:05 Hour / Min / Sec
196:10 Hour / Min